Answers and Analysis
This knowledge base, updated to include the analyses from the 2003 through the most recent editions of the Uniform Plumbing and Mechanical Codes,
continues to be a premier source for engineers, inspectors, students, contractors and tradesmen. Questions come from a broad base of users, and answers
are informal interpretations of the Codes provided by a committee of code officials and special experts - they are clearly stated and to the point.
This updated site combines the most pertinent analyses from the previous manual and presents them together with those based on the most recent
publications of the Uniform Codes. This makes the Answers and Analysis database one of the most valuable tools you as a member can access wherever you have an internet connection.
The Answers and Analysis tool makes it easy to search for relevant questions and answers, either based on keywords or specific sections/chapters of the code.
To find questions related to specific topics, type in the keyword(s), select the code and the year and click "Search".
To search for questions related to a specific section, type the section in the Section field and click "Search".
To search a specific chapter or appendix, select either the UPC or UMC Table of Contents, and select the chapter/appendix from the list.
Questions matching UPC Chapter 9
72 results
UPC 2003 904.1
UPC 2006 904.1
UPC 2009 904.1
UPC 2012 904.1
Topic: Aggregate Cross-Sectional Vent Area
Does Section 904.0 permit a normal two bathroom residential plumbing system served by a 3 inch building sewer to be vented by 2 vents each at 2 inches and one vent at 11⁄2 inches, having a total area in excess
of 8 square inches?
We are being told that some jurisdictions require a full size 3 inch vent for each 3 inch building sewer
regardless of the venting area that is provided by other vents in the structure.
Your procedure meets current UPC requirements. Although many plumbing codes still do, the UPC has not required a “main” vent stack since 1959 when an amendment accepting an equivalent aggregate area of
smaller vents was adopted. Section 904.0, therefore, relates total available vent area to the cross-sectional
area of the largest required building sewer.
UPC 2003 904.1
UPC 2006 904.1
UPC 2009 904.1
UPC 2012 904.1
There are two buildings on the same property. One building has 24 fixture units with one 2 inch vent through the roof. The second building has one 2 inch vent and one 11⁄2 inch vent through the roof. Does
this meet the requirements of Section 904.0 for vent area for a 3 inch sewer? May the buildings be separated
an indefinite distance and still be considered under the exception to Section 904.0?
Yes, the above scenario meets the requirements of Section 904.1, provided the common building sewer serves the drainage piping of the buildings which are on the same lot and under the same ownership.
There is no limitation to the distance between buildings as long as the aggregate cross-sectional area
of all vents is not less than that of the required common building sewer.
UPC 2003 904.1
UPC 2006 904.1
UPC 2009 904.1
UPC 2012 904.1
Section 904.0 reads as follows: “The size of vent piping shall be determined from its length and the total number of fixture units connected thereto, as set forth in Table 7-5 (2003/2006/2009) Table 703.2 (2012). In addition, the drainage piping of each building and each connection to a public sewer or a private sewage disposal system shall be vented by means of one or more vent pipes, the aggregate cross sectional area of which shall not be less than that of the largest required building sewer as determined from Table 7-5.” Does the following drawing comply with this requirement?
The drawing does not comply with the word or intent of Section 904.0. UPC venting requirements are intended to do two things: (1) to provide venting for all plumbing fixture traps; and (2), to provide air circulation
throughout all parts of the drainage system. To accomplish the latter, aggregate vent area equal to
the largest required building sewer must extend from the sewer through the roof. In the example, this does
not happen.
(See drawing on the following page.)
UPC 2003 904.1
UPC 2006 904.1
UPC 2009 904.1
UPC 2012 904.1
Topic: Aggregate Vent Area with Backwater Valve in System
Does the installation of a backwater valve in any part of the drainage system violate the aggregate venting requirements of the drainage system?
Yes, the installation of a backwater valve partially obstructs or diminishes the aggregate cross-sectional area of the piping between the sewer and the upper terminal of the vents.
The sewer venting required by Section 904.1 must be achieved through connection to that portion of
the drainage system which is independent of the backwater valve protected segment. This same rationale
applies when venting the sewer through a system which is equipped with a sump pump.
UPC 2003 904.1
UPC 2006 904.1
UPC 2009 904.1
UPC 2012 904.1
If a building drain is 3” and building sewer is required, by local code, to be 4” would the aggregate crosssectional area of the vent(s) need to be based on a 4” building sewer?
No. The minimum size of the building sewer is determined using Table 7-5 (2003/2006/2009) Table 703.2 (2012) of the plumbing code. Some sewers are governed by other authorities, and sewer sizes are often larger than what the plumbing code requires. Section 904.1 states that “the size of vent piping shall be determined from its length and the total number of fixture units connected thereto, as set forth in the
Table and that the drainage piping of each building and each connection to a public sewer or a private sewage disposal system shall be vented by means of one (1) or more vent pipes, the aggregate cross-sectional area of which shall be not less than that of the largest required building sewer, as determined by the Table .”
UPC 2003 904.2
UPC 2006 904.2
UPC 2009 904.2
UPC 2012 904.2
Where the fixture unit loading necessitates a 2 inch vent and structural features require an initial horizontal vent section that is 120 feet long and followed by a vertical vent section that is 60 feet long and then terminates above the roof, what are the minimum sizes and lengths of the vent pipes that are permitted by the
UPC?
The note at the bottom of Table 7-5 (2003/2006/2009) Table 703.2 (2012) limits horizontal vent sections to 1⁄3 of the total length permitted by the Table . This limitation may be waived, provided that vent pipe is increased one pipe size or more for its entire length. For this example, a 21⁄2 inch vent would be required.
UPC 2003 905.2
UPC 2006 905.2
UPC 2009 905.2
UPC 2012 905.2
Topic: Horizontal Venting Below the Flood Level
Is the installation shown in the drawing below acceptable?
No. The submitted sketch does not comply with Section 905.0 (2003/2006/2009/2012), since the vent is taken off the horizontal drainage pipe upstream of the trap being served. Also, each vent pipe must have its invert
taken off above the center line of the horizontal drainage pipe.
Horizontal venting is not acceptable less than 6 inches above the flood level of the fixture served
unless prohibited by structural conditions.
UPC 2003 905.3
UPC 2006 905.3
UPC 2009 905.3
UPC 2012 905.3
Topic: Drainage Fittings for Vents
Several plumbing contractors working within my jurisdiction have asked for an explanation of why drainage fittings are required when the venting is less than 6 inches above the flood level rim of the fixture served
as noted in Section 905.3. Please explain this code requirement.
Drainage fittings are required in vents when the venting is installed less than 6 inches above the flood rim of the fixture served, as stated in Section 905.3, because vents installed below the flood level rim of a
fixture are subject to flooding if a stoppage occurs in the drain. This flooded condition will flow from the vent
when the stoppage is cleared, provided that the vent is installed with drainage fittings. If the waste water
does not drain from the vent, the vent is not likely to remain open or clear, which could cause siphonage
of the trap and sewer gas to enter the building.
Vents installed above the flood level rim of a fixture are not subject to flooding caused by stoppages,
because the waste overflows at the fixture when a stoppage in the drain occurs.
UPC 2003 905.3
UPC 2006 905.3
UPC 2009 905.3
UPC 2012 905.3
Topic: Drainage Fittings for Vents
Does Section 905.3 require the use of a combination wye and 1⁄8 bend installed on its back as a vent connection to a horizontal drain at which point the vent is below the flood level rim of the fixture being
served?
The correct fitting to be used for this type of installation is a combination wye and 1⁄8 bend. Section 905.3 states that vents less than 6 inches above the flood level rim of the fixture shall be installed with approved
drainage fittings and material. A sanitary tee installed in a horizontal position is not an approved drainage
fitting.
UPC 2003 905.3
UPC 2006 905.3
UPC 2009 905.3
UPC 2012 905.3
Topic: Drainage Fittings for Vents
Section 905.3 states that vents less than 6 inches above the flood level rim of the fixture shall be installed with approved drainage fittings. This would then refer us to the requirements of the drainage fittings in
Section 706.0 which requires a minimum 45 degree fitting or equivalent. Does this mean that a sanitary tee
in a horizontal position may not be used as a vent connection?
Yes. Section 905.3 requires that approved drainage fittings be used for vents less than 6 inches above the flood level rim of the fixture. A sanitary tee installed in a horizontal position is not an appropriate drainage
fitting.
UPC 2003 905.3
UPC 2006 905.3
UPC 2009 905.3
UPC 2012 905.3
Topic: Horizontal and Vertical Venting
Please render an interpretation of whether a kitchen sink vent installed at 60 degrees from the vertical is permitted by the UPC. We call your attention to the definition of horizontal. We have also been asked by
the trade to call your attention to Section 706.4.
Section 706.4 (2003/2006/2009/2012) relates to drainage systems only and has nothing to do with venting. Section 905.3 addresses horizontal venting. This section requires that, unless prohibited by structural
conditions, each vent must rise vertically to a point not less than 6 inches above the flood level rim of the
fixture served, before offsetting horizontally. Then, if structural conditions do exist, such as a window, a
horizontal vent would be acceptable, provided that the horizontal portion of the vent which is less than 6
inches above the flood level rim of the fixture is installed with approved drainage material. Any angle less
than 45 degrees from the horizontal is considered horizontal by definition.
UPC 2003 905.3
UPC 2006 905.3
UPC 2009 905.3
UPC 2012 905.3
Topic: Underfloor Horizontal Venting
1. What is the definition of structurally prohibited? 2. Does this section apply to floor drains and floor sinks? 3. If a floor drain or sink is greater than 10 feet from a potential vent location, is this considered structurally
prohibited (refer to Table 10-1 (2003/2006/2009) Table 1002.2 (2012))?
4. If a vent line does offset below the flood rim level, is a wall cleanout required at the rise above the floor
level?
1. The intent of the phrase unless prohibited by structural conditions is not to prevent digging, drilling, sleeving, or chipping, but may be used where the depth of the sewer or the design of the building
provides no other way and where the installation of the horizontal vent 6 inches above the flood rim of
the fixture would weaken the structure, such as by the excessive cutting or notching of the required
beam. Structural conditions include walls or the practical points of vent rise located at greater distances
from traps than the trap arm length as permitted by Table 10-1 (2003/2006/2009) Table 1002.2 (2012); space limitations between ceilings and floors; interference with beams or girders and lack of initial available drain depth.
2. Yes.
3. Yes.
4. No, however, vents less than 6 inches above the flood level rim of the fixture must be installed with
approved drainage fittings, materials, and grade to the drain.
UPC 2003 905.3
UPC 2006 905.3
UPC 2009 905.3
UPC 2012 905.3
Topic: Water Closet Venting
Referring to the illustrations below with the closet bends installed as shown, would either of these methods of venting a water closet be considered as acceptable under “normal circumstances”?
No. There are two reasons why the submitted examples do not comply with the code and are not acceptable. The closet bend as shown would be required to be 45 degree fittings or equal (Section 706.4,
2003/2006/2009/2012) and the horizontal vent less than 6 inches above the flood rim of the fixture is only
permitted when required by structural conditions (Section 905.3), which the drawing does not show.
The intent of the phrase unless prohibited by structural conditions is not to be used to prevent digging,
drilling, sleeving, or chipping, but may be used where the depth of the sewer or the design of the building
provides no other way and where the installation of the horizontal vent six inches above the flood rim of
the fixture would weaken the structure such as the excessive cutting or notching of a required beam. The
"UPC Illustrated Training Manual" shows acceptable methods of venting a water closet.
UPC 2003 905.3
UPC 2006 905.3
UPC 2009 905.3
UPC 2012 905.3
Topic: Horizontal Venting
Section 905.3 requires each vent to rise vertically 6 inches above the flood level rim of the fixture served. In a back-to-back installation, would the horizontal vent be permitted to be run below the overflow of the
bathtub, when the horizontal vent is 6 inches above the overflow of the shower pan (see drawing below)?
No, unless prohibited by structural conditions, a common vent that serves two or more fixtures must rise vertically to a point not less than 6 inches above the flood level rim of the highest fixture served, before
offsetting horizontally.
UPC 2003 905.3
UPC 2006 905.3
UPC 2009 905.3
UPC 2012 905.3
Topic: Horizontal Venting of Fixtures Below Fixture Flood Rims
Can a sink vent be horizontally offset below the flood rim of the sink?
When unavoidable structural conditions prohibit vertical rise (minimum 6 inches above the flood level rim of the fixture), the first alternative would be a longer trap arm. Should the conditions prohibit this, the horizontal portion of the vent must be raised as high as possible, graded back to the drain, and utilize drainage fittings for all portions of the vent.
UPC 2003 905.3
UPC 2006 905.3
UPC 2009 905.3
UPC 2012 905.3
Topic: Special Venting for Island Fixtures
Is there anything that prevents the island loop venting method from being used for a kitchen sink that is installed under a window at an exterior wall?
Yes. Section 905.3 requires vents to rise vertically and makes allowances for running the vent below the flood rim of the fixture using drainage fittings. Island venting (Section 909.0) is specifically designed for
sinks and similar equipment, mounted in an island, which is a fixture not connected to an adjoining wall
that would allow the installation of a conventional waste and vent system. Inconvenience is not a reason
to allow this type of installation.
See also 909.0
UPC 2003 905.3
UPC 2006 905.3
UPC 2009 905.3
UPC 2012 905.3
Topic: Vent Pipe Grades and Connections
Can vent lines be installed below slab as long as they are sloped back to the sewer line (1/4” per foot slope)
Yes. Section 905.2 of the UPC states that “where vents connect to a horizontal drainage pipe, each vent pipe shall have its invert taken off above the drainage centerline of such pipe downstream of the trap being served”. Additionally, vents that offset horizontally below the flood-level-rim of the fixture being served shall be installed with approved drainage fittings, material and grade to the drain.
UPC 2003 905.4
UPC 2006 905.4
UPC 2009 905.4
UPC 2012 905.4
Section 905.4 states that “all” vent pipes shall extend undiminished in size above the roof, or shall be reconnected with a soil or waste vent. Could you explain the reason for this and the intent of the Code
The word undiminished is intended to prevent reduction of the required cross-sectional area of any section of a vent or vent piping system between its point of origin and its terminus.
The intent of this section is to assure that individual or combined vent pipe systems have the individual
or aggregate area needed to prevent pressure migrations within the waste vent system in excess of a one
inch water column.
(See the drawing on the following page.)
UPC 2003 905.5
UPC 2006 905.5
UPC 2009 905.5
UPC 2012 905.5
Topic: Double Wyes as Fixture Tees
Is it permissible to use a double wye in lieu of a double fixture fitting for side-by-side lavatories?
No. Except for water closets and similar fixtures, a double wye is not acceptable as a double fixture fitting for back-to-back or side-by-side installations. Listed double fittings for such installations are designed so
the vent opening is above the weir of the trap to prevent trap siphonage and sewer gas from entering the
room or building.
UPC 2003 906.1
UPC 2006 906.1
UPC 2009 906.1
UPC 2012 906.1
In the case of constructing a new gable roof over an existing flat roof on an apartment complex, are there any circumstances that would allow a plumbing vent to terminate below the new roof? Would the open
sides and ends have any affect on waiving the termination requirements?
No. Any vent that does not terminate vertically 6 inches or more above the roof, as required in Section 906.1, is not acceptable. The open sides or ends in the building as described do not have any effect on
waiving termination requirements. Sewer gas is too dangerous and unsanitary to allow in any part of a
building or structure.
UPC 2003 906.1
UPC 2006 906.1
UPC 2009 906.1
UPC 2012 906.1
Topic: ABS Vents Penetrating Flashing
Could ABS pipe that is installed through a galvanized vent flashing be subject to wear or cause any problems?
There is no doubt that the pipe is exposed to sharp surfaces where it passes through the flashing. However, because of the function and configuration of the flashing, it is doubtful that the exposure to its
sharp surfaces could result in perceptible damage during installation, or as a consequence of long term
service.
Additional protection for the ABS pipe is not required where it passes through a metal flashing.
see also 313.5 (2003/2006), 313.4 (2009) 312.4 (2012) and IS 5
UPC 2003 906.2
UPC 2006 906.2
UPC 2009 906.2
UPC 2012 906.2
Regarding Section 906.2, does the word opening mean an opening that would provide for the inflow of sewer gases into a habitable area of a building or structure, and would not include such openings as eaves,
gables or dormer vents?
Any sanitary vent that terminates less than 10 feet from or 3 feet above any opening into the building where sewer gas could enter the building is a violation of the Code. The word opening does include such openings
as eaves, gables, and dormer vents in attic and joist areas. The committee is aware that the building
code does not require an access opening from the habitable area under certain conditions, but the potential
of dangerous and hazardous sewer gas entering any part of the building is not acceptable.
UPC 2003 906.3
UPC 2006 906.3
UPC 2009 906.3
UPC 2012 906.3
Topic: Flagpoling of Vents
Section 906.2 requires that a vent terminate not less than 10 feet from, or at least 3 feet above any openable window, door, opening, air intake, or vent shaft. With regard to Section 906.3, for a vent terminating
above a roof that is used only for weather protection, is there a specific distance that a vent may rise before
it is considered as being flagpoled?
Flagpoling, as used in Section 906.3, is a term defining any vent that exceeds the minimum vertical distance required above the roof and requires additional support such as guy wires, brackets, or other
means of restraining movement.
The local Authority Having Jurisdiction is required to determine if a vent is flagpoled, since several
factors have to be considered, such as, type of material, pipe size, and location of joints below the roof.
UPC 2003 906.3
UPC 2006 906.3
UPC 2009 906.3
UPC 2012 906.3
Flagpoling is limited in use according to UPC 2009. What is the IAPMO definition of flagpoling?
Flagpoling was defined in the 2006 Illustrated Training Manual (ITM) as “any vertical vent pipe that has more of its total length above the roof penetration (fulcrum) than below it shall be defined as ‘flagpoled’. This mechanical advantage may result in wind or physical contact causing displacement of the piping both above and below the roof penetration.” Sometimes because of structural conditions a vent may have to be extended to a point of termination above an air intake into a building or above a window or door as required by section 906.2. In such cases the vent would be required to be secured in such a way as to prevent it from swaying in windy conditions which could eventually cause the vent pipe to fail and break off at surface of the roof.
UPC 2003 908.1
UPC 2006 908.1
UPC 2009 908.1
UPC 2012 908.1
Topic: Vertical Wet Venting
Section 908.1 states, “Wet venting is limited to vertical drainage piping receiving the discharge from the trap arm.” This would lead me to believe that wet venting is limited to the trap arm discharge only but then
it states further that "fixtures with a continuous vent discharging into a wet vent shall be on the same floor
level as the wet vented fixtures." Do the proposed drawings (see below) comply with the vertical wet
venting requirements of Section 908.1?
Section 908.1 requires wet venting to be limited to vertical drainage piping receiving the discharge from
trap arms only. The term continuous vent applies to the vent above the top fixture only of an assembly of
wet vented fixtures.
Therefore, your proposed drawings do not comply with the vertical wet venting requirements of Section
908.1.
UPC 2003 908.1
UPC 2006 908.1
UPC 2009 908.1
UPC 2012 908.1
Can a branch line serving four plumbing fixtures connect to a vent serving a water closet?
No. Wet venting is limited to vertical drainage piping receiving the discharge from the trap arm of one and
two fixture unit fixtures.
UPC 2003 910.1,
UPC 2006 910.1,
UPC 2009 910.1,
UPC 2012 910.1,
Topic: Venting of Branches for Combination Waste and Vent Systems
Can two traps be installed on one branch without reventing on a combination waste and vent system?
Yes, provided that the branch serving more than one trap on a combination waste and vent systems does not exceed 15 feet in length and has a cleanout installed at its upper terminal, as required by Section 910.6.
See also Appendix B
UPC 2006 908.4
UPC 2009 908.2
UPC 2012 908.2
Topic: Horizontal Wet Vent
Is there a length restriction placed on the horizontal wet vent in 908.4(2006), 908.2 (2009/2012)?
Section 908.4 (2006)908.2 (2009/2012) code does not address a length maximum for the horizontal wet vent. The length of trap arms that connect to the horizontal wet vent must comply with the lengths shown in Table 10- 1. Table 7-5 states that the length of drainage piping is unlimited while the length of horizontal vents is limited to 1/3 of the total length allowed. (40 feet for 2 inch and 70 feet for 3 inch) It seems highly unlikely that these limits would be exceeded in a bathroom group.
UPC 2006 908.4.3
UPC 2009 908.2.1.2
UPC 2012 908.2.2
Topic: Horizontal Wet Vent
Does the piping upstream of the water closet need to be 3" even though the fixture unit DFU is 4 or less?
Section 908.4.3 (2006), 908.2.1.2 (2009), 908.2.2 (2012) UPC allows four (4) DFU units on a 2 inch horizontal wet vent. The total DFU values affixed to a bathtub and lavatory is 3 DFU per Table 7-3 (2006/2009), Table 702.1 (2012). A 2” wet vent would be permissible by Code.
UPC 2009 908.2
UPC 2012 908.2
Topic: Horizontal Wet Vent
1. Is a half bath considered a bathroom group?
2. A. If you choose to horizontal wet vent 1 and/or 2 bathroom groups, are all fixtures, as defined under "bathroom group", required to be horizontally wet vented?
B. Can you choose any combination of bathroom group fixtures to be on the horizontal wet vent (i.e. horizontal wet vent just the tubs and lavs, or toilets and lavs)?
3. 908.2.1-"Only one wet-vented fixture drain or trap arm shall discharge upstream of the dry-vented fixture drain connection." Would 2 lavs on two separate trap arms that tie together with a fixture cross be allowed?
1. Yes. Based on a TIA that has been issued by IAPMO, for section 204.0, any combination of one water closet, one or two lavatories, and either one bathtub, or one combination bath/shower, and one shower, and, may include a bidet and an emergency floor drain, defines a bathroom group. Hence one water closet and one lavatory is “a combination of…”.
2. A. No. The code does not restrict a fixture from being plumbed conventionally, as long as they are fixtures that are defined as allowed in a bathroom group.
2. B. Yes. The code states “any combination.” of fixtures may be served by the horizontal wet vent. Note that lavatories with traps above the floor must be conventionally vented and may serve as the dry vent for the system.
3. Yes, the vent for the two lavatories would be considered a common vent and would be permitted to vent the bathroom group(s) provided they are the upstream fixtures or immediate downstream fixtures. For example; A tub or shower trap arm could be the upstream fixture with the two lavatories located immediately downstream to act as the vent for the bathroom group(s).
UPC 2009 908.2
UPC 2012 908.2 TIA 001-12
UPC 2015 908.2
Topic: Horizontal Wet Vent
In a horizontal wet vent for bathrooms groups is it required for any part of the wet vent to have its invert above the center line of the drain?
No. In August 2012 a TIA was issued by IAPMO to revise the language in the code regarding horizontal wet vents. Part of the change removed the mandatory language requiring all of the connections to the wet vent to be horizontal. New wording simply requires the connections to be above the weir of the trap and could be either horizontal or above the center line of the drain. The requirement for a vent to connect above the center line of the drain applies to all dry vents that connect to the horizontal wet vent or a horizontal fixture drain.
UPC 2009 908.2
UPC 2012 908.2
UPC 2015 908.2
Topic: Horizontal Wet Venting
In the horizontal wet venting section 908.2, is the portion of the dry vent (connected to a lavatory drain) above the finished floor required to remain vertical?
Once the vent becomes a dry vent it will need to meet the requirements found in Section 905.3, which states that “Unless prohibited by structural conditions, each vent shall rise vertically to a point not less than 6 inches above the flood-level rim of the fixture served before offsetting horizontally... Vents less than 6 inches above the flood-level rim of the fixture shall be installed with approved drainage fittings, materials, and grade to the drain.”
UPC 2009 908.2; 905.2
UPC 2012 908.2, 905.2
UPC 2015 908.2, 905.2
Topic: Horizontal Wet Venting
Does the wet vent connection to the branch drain have to connect above the centerline of the branch drain? Or can the entire bathroom group have a 1/4" slope?
1. No. Only dry vent connections to the horizontal wet vent are required to have its invert taken off above the drainage centerline in accordance with Section 905.2.
2. All the piping and trap arms need to maintain the ¼” slope.
UPC 2009 908.2.2
UPC 2012 908.2 .1
UPC 2015 908.2.1
Topic: Horizontal Wet Venting
1. Does a toilet, a tub-shower or tub, shower and 1 or 2 lavatories have to discharge into that horizontal wet?
2. Can just a shower wash the horizontal wet vent for a toilet, without the addition of a lavatory to the wet vent?
3. Can just a toilet and lavatory be included into a horizontal wet vent without the tub or shower if the bathroom is a bathroom group?
4. Please explain 908.2.2 (2009) 908.2.1 (2012/2015) The dry vent connection to the wet vent shall be an individual vent for the bidet, shower, or bath tub. One or two vented lavatories shall be permitted to serve as a wet vent for a bathroom group.
1. No. A water closet and any combination of a tub/shower, tub, shower, or 1 or 2 lavatories may be part of a wet vent installation. The key to a horizontal wet vent is that a fixture with a dry vent has a waste line appropriately sized to provide a vent for the horizontal wet vent piping system.
2. Yes, see answer 1
3. Yes, see answer 1
4. A dry vent, pertaining to a horizontal wet vent system, is the portion of the waste and vent piping for a lavatory(s), tub/shower, or tub, which is connected to the waste piping for the aforementioned fixtures and is located above the weir of the trap of that fixture. It is used to provide air for both the fixture and the horizontal wet vent piping system.
UPC 2009 908.2
UPC 2012 908.2
UPC 2015 908.2
Topic: Horizontal Wet Venting
Does a water closet always have to be part of a horizontal wet vent, or can there be other combinations of fixtures without a water closet?
Horizontal wet venting is limited to any combination of fixtures within a bathroom group as defined in section 204.0
UPC 2009 910.3
UPC 2012 910.3
UPC 2015 910.3
Topic: Combination Waste and Vent Systems
Section 910.3 says the vent connection shall be downstream of the uppermost fixture. Additionally, Appendix B says a relief vent is required every 100 feet.
Does the “terminal vent” have to be located immediately downstream of the uppermost fixture, or can it be anywhere downstream?
Comment
Figure 9-37(2009), 910.3A (2012/ 2015) in the Illustrated Training Manual shows it immediately after the uppermost fixture, but Section 910.3 does not read that way.
Section 910.3 of the UPC specifically requires the upper terminal vent for a combination waste and vent system to be connected to the waste piping downstream of the uppermost fixture. Figure 9-37 (2009), Figure 910.3A (2012/ 2015) in the Illustrated Training Manual is drawn per that requirement. Although not stated in the code, Figure 9-41 (2009), Figure 910.5B (2012/ 2015) shows that the maximum distance from the uppermost fixture trap to the vent to be 15 feet. Table 10-1 (2009), Table 1002.2 (2012/ 2015) shows allowable trap arm to vent distances for a standard waste and vent system.
Note: Only if Appendix B has been adopted, as specified in Section 103.8.2 (2009), 101.10 (2012), 102.8 (2015) would the provisions of Appendix B apply to the installation.
UPC 2006 908.4.2
UPC 2012 908.2.1.1
UPC 2015 908.2.1
Topic: Horizontal wet venting
On horizontal wet vent is a tub or shower permitted to be on the vertical where wet and dry connection is made? Or is only a single lav or two lavs permitted to be on the vertical wet to dry connection?
Comment
All I see on examples are lavs on the horizontal wet vent to vertical dry connections and reading this note in section 908.2.1.1 reads as towards Shower, tubs, or bidets must not be the wet vertical fixture on a horizontal wet vent.
Yes, Section 908.2.1 of the 2015 UPC permits the dry vent for the horizontal wet vent to be an individual vent from a bidet, shower or bathtub as well as a lavatory. Drawings 1 and 3 appear to be code compliant.
UPC 2012 908.3
UPC 2015 908.2.1
Topic: Horizontal Wet Venting
When using horizontal wet venting:
1. May the fixture branch serving a water closet discharge “straight through” the inlet (not the wye branch) of the wye fitting?
2. Must the fixture branch for a water closet come off the wye branch of the fitting?
Comment: I being told it can be either way.
Fittings for horizontally wet vented drainage systems are not required to be “taken off above the drainage centerline” as required for individually vented horizontal fixtures as found in Section 905.2 of the 2012 UPC. Without that requirement, the fixture may be connected to the run (straight through) or branch of the fitting.
UPC 2006 906.1
UPC 2012 906.1
UPC 2015 906.1
Can plumbing vents be installed beneath solar panels on a flat roof where the solar panels are mounted three (3) feet above the roof surface?
The 2012 Uniform Plumbing Code does not address the installation of plumbing vents below solar panels. Good plumbing practice would suggest avoiding this type of installation. In the event there is no other solution to the problem there should be adequate space between the vent opening and solar panel to allow adequate air circulation in the DWV system as prescribed in Section 901.1. Plans should be submitted to the AHJ for approval as an alternate method of construction, to assure the installation meets the intent of the code.
UPC 2006 908.4
UPC 2009 908.2
UPC 2012 908.2
UPC 2015 908.2
UPC 2018 908.2
Topic: Horizontal Wet Venting for a Bathroom Group
1. Does the 6 foot limitation for vertical wet venting also apply to horizontal wet venting for a bathroom group?
2. Are there any length limitations for horizontal wet venting?
1. No. The 6 foot length limitation for vertical wet venting is to ensure that the wet vented sections remains within a single story as required in Section 908.1 of the 2018 Uniform Plumbing Code.
2. Yes. Per Section 908.2.3, trap arms are limited to the lengths found in Table 1002.2. The Code has no other length limitations for horizontally wet vented bathroom groups.
UPC 2015 911.5
UPC 2018 911.5
Topic: Circuit Venting, Additional Fixtures
1. Is there a problem if the additional fixtures were sets of back to back lavs upstream of the circuit vented fixtures? (See Drawing)
It is the opinion of this Committee that the submitted illustration meets the intent of Section 911.0 of the 2015 Uniform Plumbing Code.
UPC 2009 908.2
UPC 2012 908.2
UPC 2015 908.2
UPC 2018 908.2
Topic: Horizontal Wet Venting for a Bathroom Group
If a floor drain is installed in a bathroom that has a water closet, lavatory, and bathtub horizontally wet vented, is the floor drain considered as an emergency floor drain and does the floor drain need to be individually vented?
The floor drain is considered an emergency floor drain and is included in the definition of a bathroom group and if installed per Section 908.2 of the 2018 Uniform Plumbing Code, would not need to be individually vented.
UPC 2018 908.1.1
Topic: Vertical Wet Venting Sizing
1. Is there an error in sizing the branch piping from the Laundry Sink and Clothes Washer group in Figure 908.2A of the 2018 UPC ITM (page 298)?
2. The vertically wet vented section needs to be increased to one pipe size larger than 2”, which is normally required for a 2 fixture unit sink drain, correct?
Comment:
In FIGURE 908.2A on page 298 of the 2018 UPC ITM, the pipe size for the drainage branch receiving the discharge from the clothes washer and laundry tray is labeled as 2”.
1. Yes. The minimum drain size for the Laundry Tray(2DFU), per Table 703.2 of the 2018 Uniform Plumbing Code is 2”. Section 908.1 states that each wet-vented section shall be not less than one pipe sizing larger than the minimum pipe size required per Table 703.2. The required wet vent section would therefore be required to be 3”.
2. Yes. The wet-vented section and downstream piping is required to be 3”.
UPC 2015 905.0, 905.2
Topic: Vent Pipe Connection to Horizontal Drainage Pipe
Would a sanitary tee be an approved fitting where a vent connects to a horizontal drainage pipe below a floor, provided the installation of the branch of the tee, used for the vent connection, conforms to Section 905.2?
Comment
Section 903.3 indicates that changes in direction of vent piping shall be made with appropriate use of approved fittings.
No. Section 905.3 of the 2015 Uniform Plumbing Code states that “Vents less than 6 inches above the flood-level rim of the plumbing fixtures it serves shall be installed with approved draining fittings, material, and grade to drain.” Sanitary Tees are only considered drainage fittings when installed in the vertical position.*
*2015 UPC, 706.2 Horizontal to Vertical. Horizontal drainage lines, connecting with a vertical stack, shall enter through 45 degree (0.79 rad) wye branches, 60 degree (1.05 rad) wye branches, combination wye and one-eighth bend branches, sanitary tee or sanitary tapped tee branches, or other approved fittings of equivalent sweep. No fitting having more than one inlet at the same level shall be used unless such fitting is constructed so that the discharge from one inlet cannot readily enter any other inlet. Double sanitary tees shall be permitted to be used where the barrel of the fitting is not less than two pipe sizes larger than the largest inlet, (pipe sizes recognized for this purpose are 2 inches, 21⁄2 inches, 3 inches, 31⁄2 inches, 4 inches, 41⁄2 inches, 5 inches, 6 inches, etc.) (50 mm, 65 mm, 80 mm, 90 mm, 100 mm, 115 mm, 125 mm, 150 mm, etc.).
UPC 2015 907.1
Topic: Vent Stacks and Relief Vents
1. Is the interpretation now to provide parallel vent stacks for all stacks regardless of how long the offset are?
2. Do these stacks require parallel vent stacks?
Comment:
1. Language from Section 907.1 "above the building drain or other
horizontal drain" was deleted.
2. In a condition, where stacks step down the building, and the offsets are 30'-60' horizontal at every other 3-4 floors (see attached sketch).
1. No. The deletion of the stated language does not change the interpretation of Section 907.1 of the 2015 Uniform Plumbing Code. A drainage stack* less than 10 stories in length is not required to have a parallel vent stack with a yoke vent. Additionally, past interpretations of this section recognize horizontal offsets within the stack, regardless of the length of the offset, as a means of eliminating the need for the yoke vent.
2. No
*Stack. The vertical main of a system of soil, waste, or vent piping extending through one or more stories
UPC 2009 906.0
Does Section 906 or any other section of the 2009 UPC require a vent to penetrate the roof, or is it acceptable to penetrate a wall of building as long as the vent terminates least 6” above the roof?
Section 906.1 of the 2009 Uniform Plumbing Code (UPC) states, “Each vent pipe or stack shall extend through its flashing and shall terminate vertically not less than six (6) inches above the roof nor less than one (1) foot from any vertical surface”. Though the 2009 UPC does not define “flashing”, it can best be described as an impervious material that is used in building construction to prevent water from passing into a structure through an exterior penetration. Although flashings for plumbing vents are usually designed for roof penetrations, side wall flashings do exist. Vents penetrating the side wall of a structure, by means of a flashing, would be permitted if installed to the requirements found in Section 906.0.
UPC 2015 908.2.1, 905.2, 905.3
Topic: Horizontal Wet Vent Connection
When using Section 908.2.1, can 905.3 be ignored and use 905.2 to comply with the dry vent connection to the wet vent?
Comment:
No lav to scour the vent in this application.
No. Per Section 908.2.1 of the 2015 Uniform Plumbing Code, “Dry vent connections to the horizontal wet vent shall be in accordance with Section 905.2 and Section 905.3”. A dry vent would be required to meet both referenced code sections.
UPC 2015 906.1
Is it permissble to install grates above sanitary vents that penetrate and terminate above the roof at least 6 inches?
Comment:
The sanitary vents terminate a minimum of six inches above roof. The grates have openings that are 1/2 inch minimum and do not impede or restrict airflow or circulation around vent termination.
Yes, with the following conditions:
1. There is adequate space between the vent openings and grate to provide free movement of air as required in Section 901.2 and of the 2015 Uniform Plumbing Code.
2. The vent termination meets the requirements found in Section 906.1.
3. The opening on the upper portion of the walkway would require the vent locations, per Section 906.2, to be a minimum of 10 feet away from the walk-way or be raised as required in Section 906.3, to a minimum of 7 feet above the roof.
Note: This installation would not be acceptable in areas where snow or frost could cover the grates thereby restricting the circulation of air in the space between the roof and grate.
UPC 2015 911.0
1. After the circuit vented section can the drain line continue to catch upstream fixtures on the same floor?
2. After the circuit vented section can the drain line continue to catch upstream stacks to upper floors?
3. Or do the stack need to be downstream of the circuit vented section?
Comment:
On circuit venting you can tie in drains to fixture on the same floor to the circuit vent. (example: in a public bathroom where the WC's are circuit vented I can tie in my lav drains to the circuit vented section.)
1. Yes. Section 911.5 of the 2015 Uniform Plumbing Code(UPC)states “fixtures other than the circuit-vented fixtures, are permitted to discharge to the horizontal branch drain. Such fixtures shall be located on the same floor as the circuit-vented fixtures and shall be either individually or common vented”.
2. Per Section 911.5, additional fixtures located on the same floor, may discharge either upstream or downstream of a circuit-vented branch. Waste piping receiving the discharge from fixtures on upper floors would be approved to be connected to the common waste line downstream of the circuit-vented branch.
UPC 2012 910.0
Topic: Combination Waste and Vent Systems
1. Are the pipe sizes labeled in Figure 910.7 (attached) minimum pipe sizes per section 910.7?
2. If "yes", why is the pipe size (asterisk No.1 of the attachment) serving 6 DFUs downstream of the terminal vent a 4” rather than a 3”?
3. Is the interpretation that the min. size vent for the CWV is 3”, thus, the waste run is being used as a vent for the CWV system, and to 4” for proper venting of the CWV system? Is this correct?
4. If the answer to 3 is yes, please explain the reason the 3” waste line wye (asterisk No. 2 in attachment) connecting to the 4” main waste run with the min 2-1/2” VTR? Is this another CWV system? If so, the min. determined terminal vent is 2-1/2”, and the waste run is used as the vent for the CWV system, why wouldn't this be two pipe size larger,(3-1/2”) but shown to be 3”?
5. If this is not a combination W/V system, but because the fixtures exceed the 15 feet max distance, why wouldn't both fixtures be vented?
Comment:
I’m questioning why the “main drain” line is 4” when there are only 15 dfu discharging and the branches have already been increased 2 pipe sizes as required.
Thank you for your time and assistance in this matter so I can provide guidance to designers/local code officials
1. No. The minimum size waste line downstream of the upper terminal vent would be 3” per Section 910.4 of the 2012 Uniform Plumbing Code*.
2. The 4” waste line after the upper terminal vent is larger than required by code. The purpose of the increase is twofold. 1) To eliminate the need for an additional vent that would be required at the 4” connection of the most downstream floor drain as required in the Section 910.3. 2) To provide only one 3-1/2” cleanout for the entire combination waste and vent system per Table 707.1.
3. Yes.
4. By definition, a trap arm is the “portion of a fixture drain between a trap and the vent”. The vent for a combination waste and vent system is the main waste line. The referenced pipe section therefore has two traps on one trap arm which conflicts with Section 1001.1, that permits only one trap per trap arm. By installing a vent on the uppermost fixture, over sizing the traps and drains, the installation would be considered a combination waste and vent system.
5. Since there are no length measurements on the piping, we must assume that the lengths are within the 15 foot limitation. The branch is considered a combination waste and vent system and as such shall meet the requirements of Section 910.3.
*Note: The entire combination waste and vent system has a drainage fixture unit load of 10 DFU. Each floor drain has a 3” trap which means the riser, being two pipe sizes smaller, would be 2”. A 2” floor drain, per Table 702.1 is 2 DFUs. Due to the oversizing requirements of the combination waste and vent system, the main waste line must be increased to 4” only after the last floor drain is connected to the system.
UPC 2018 908.2
Topic: Horizontal Wet Venting for a Bathroom Group.
In reference to note #1 in the attached diagram, is the piping illustrated correct by allowing the piping downstream of the horizontally wet-vented fixtures to drain vertically before the water closet connection? Secondly, in reference to note #2 in the same attached diagram, is the piping illustrated correct by allowing the wye branch of the horizontally wet-vented piping to be rolled up provided the angle does not exceed 44 degrees?
1. No. The purpose of a horizontal wet vent, is to permit multiple fixtures to be served by a common horizontal waste line* that also acts as the vent for the fixtures. The connection of fittings to a horizontal wet vented system, as indicated by the system’s description, are intended to remain horizontal. The water closet in this illustration is clearly installed on the vertical stack.
2. Yes. The fitting is not required to be rolled up to be code compliant. By definition, a fitting that is less than 45 degrees with the horizontal is still considered horizontal.
* Section 210.0 - Horizontal Pipe. A pipe or fitting that is installed in a horizontal position or which makes an angle of less than 45 degrees (0.79 rad) with the horizontal.
UPC 2015 905.3
1. Does the vent below the flood-level rim of the fixture require 1/4" per foot slope?
2. If structural conditions prohibit the use of 1/4" per foot slope, is it permitted to use 1/8" per foot slope or less?
Comment:
UPC Section 905.3 states: "Vents less than 6 inches above the flood-level rim of the fixture
shall be installed with approved drainage fittings, material, and grade to the drain."
1. Yes. Section 905.3 of the 2015 Uniform Plumbing Code states that, “Vents less than 6 inches above the flood-level rim of the fixture shall be with approved drainage fittings, material, and grade to the drain”. Per Section 708.1, horizontal drainage pipe shall be run in a uniform slope of not less than 1/4 inch per foot to the point of disposal.
2. Although the Code does not specifically grant the Authority Having Jurisdiction (AHJ) the power to waive the requirements of the Code, deviation from the minimum slop of ¼ inch per foot slope for horizontal drainage pipe due to structural issues may, with the approval of the AHJ, warrant a onetime variance.
UPC 2018 911.0
Can a battery of wall hung water closets on the same horizontal branch line be circuit vented?
Comment:
Don’t see anything in 911.0 addressing wall hung water closets.
Yes. Section 911.0 of the 2018 Uniform Plumbing Code (UPC), does not specify the type or configuration of fixtures that are permitted to be installed on a circuit vented system.
Note: The 2021 UPC limits the fixtures installed on a circuit vent to water closets, showers, bathtubs, or floor drains. Additionally, when back-outlet or wall-hung water closets are installed on a circuit vented system provided no floor-outlet fixtures are connected to the same horizontal branch.
UPC 2015 911.1
Is circuit venting allowed for fixtures prior to discharging into grease interceptor?
Comment:
Section 1014.1.1 Trapped and Vented. "Each fixture discharging into a grease interceptor shall be individually trapped and vented in an approved manner."
Section 911.1 Circuit Vent Permitted "A maximum of eight fixtures connected to a horizontal branch drain shall be permitted to be circuit vented. Each fixture drain shall connect horizontally to the horizontal branch being circuit vented. The horizontal branch drain shall be classified as a vent from the most downstream fixture drain connection to the most upstream fixture drain connection the horizontal branch."
No where in the code says a grease-producing potential, restaurant kitchen equipment can not utilize circuit venting. Combination, Waste and Vent systems is the only system addresses not to be used for grease - producing potential, restaurant kitchen equipment, Appendix B section B 101.2.
See illustration
No. Section 1014.1.1 of the 2015 Uniform Plumbing Code, specifically states that “each fixture discharging into a grease interceptor shall be individually trapped and vented in an approved manner”.
Note: The 2021 UPC limits the fixtures installed on a circuit vent to water closets, showers, bathtubs, or floor drains.
UPC 2012 906.1
Topic: Air Admittance Valves
Are air admittance valves allowed to be used for venting without taking the vent above the roof?
No. The 2012 Uniform Plumbing Code, does not permit air admittance valves as an acceptable means of venting a drainage system. Section 901.1 requires air circulation throughout all parts of the drainage system by means “vent pipes installed in accordance with the requirements of this chapter and as otherwise required by this code”. This includes termination of each vent pipe through the roof as required in Section 905.4.
Note: Mechanical “check valve” type fittings allow air flow into the waste and vent system when the drain is flowing. Air is unable to flow out through these fittings, thus positive pressure generated downstream of the liquid flowing in the drain line is unable to escape through these “vents”. The purpose of a venting system is to allow air flow to occur in both directions, there stabilizing internal system pressures. Any fitting on a vent pipe which limits air flow to one direction conflicts with basic objectives of a vent piping system.
UPC 2012 907.1
1. Is the yoke-vent size based on the size of the vent and/or waste stack where it occurs?
2. Or Is the yoke-vent size based on the overall size (at the base) of the waste stacks?
Comment:
Example: High-rise building, the vent stack is 4" (undiminished in size) and the waste stack is 2" at the top and 6" at the base. If the yoke-vent is equal to the size of the vent stack and/or waste stack where it occurs. Then in this situation, the top of the stack (5th floor down) the yoke-vent would be 2", then at the base of the stack the yoke-vent would be 4".
Or If based on the overall stack, should the yoke-vent always be 4" in the above-described situation?
The sizing of both the drain and vent stack is determined by the number of fixture units being served by the stacks. The size of the yoke vent connection between the two stacks is controlled by the diameter of the smallest stack. Typically, the parallel vent stack will be larger than the drain stack at the upper floors. The diameter of the drain stack connection will then determine the size of the yoke vent connection. As the drainage stack increases in size, so the must the yoke vent connection.
UPC 2012 911.0
Topic: 911.0 Engineered Vent System.
If a registered design professional provides calculations for an engineered vent system, in accordance with Section 911.0, that provides for using a 1-1/2" individual vent for a water closet is that acceptable even though Table 703.2 requires a minimum of a 2" vent?
No. Section 301.4 of the 2012 Uniform Plumbing Code does allow an alternate engineered design for plumbing system, but also states that the design shall comply with the intent of the provision of the code and shall provide an “equivalent level of strength, effectiveness, fire resistance, durability and safety”. Reducing the size of the vent from 2” (which is required per Table 703.2)to 1-1/2” will not provide an equivalent level of effectiveness.
Note: Jurisdictions that have adopted Appendix C (Alternate Plumbing Systems)may accept engineered plumbing systems sized per the requirements found in that appendix.
UPC 2018 908.2
Topic: Horizontal Wet vent design
When installed as part of Horizontal Wet Vent design, can the trap arm for a water closet offset vertically with 2-45's?
Comment:
In the attached sketch, assume the pitch of all piping is code compliant. Is this allowed or does the closet bend have to be lengthened to the correct elevation? See linked image.
No. Section 908.2 of the 2018 Uniform Plumbing Code gives specific requirements for the installation of a horizontal wet vent for a bathroom group. By definition, a horizontal pipe is “a pipe or fitting that is installed in a horizontal position or which makes an angle of less than 45 degrees with the horizontal.” By using 45° fittings, the offset to the water closet is no longer horizontal but would be considered vertical.
UPC 2018 906.3
We are designing a space for a pump station which is completely underground. Would it be acceptable, per section 906.3, for the plumbing vents to terminate 12 inches above the surface of the ground that is essentially serving as a roof for the space? The vents will have vandal-resistant, cast iron, hoods.
Comments
The pump station includes floor drains and indirect waste receptors to collect water that is discharged during maintenance and from small leaks that might occur. The piping from
these fixtures is collected in a vented sump and pumped to the municipal sewer.
We believe the plumbing venting for this installation would be similar to a roof, when the roof is not used for assembly purposes or parking, because neither of these functions will occur on the ground above the pump station. The ground in this area will be unpaved. There is parking for maintenance vehicles on grade outside the footprint of the pump station but not over the station. As long as the vent terminations are more than 10 feet from this parking area they will not need to be extended seven feet above the surface.
We believe that 906.4 is not applicable because the vent terminations in question serve installations (plumbing fixtures) that are indoors (within the pump station), not outdoors.
The concrete slab may be the roof for the underground pump station, but the slab itself is located slightly above ground level. Permitting vents to terminate 12 inches above the slab would create a health hazard* for anyone in the vicinity of the pump station. Although the 2018 Uniform Plumbing Code does not specifically address this type of installation, Section 102.5 permits the Authority Having Jurisdiction the discretion to require alterations to plumbing systems to alleviate a nuisance or other dangerous or insanitary conditions that involves health or safety hazards.
Note: It is the opinion of this Committee that the requirements found in Section 906.4 would be the most applicable for this type of installation.
*Sewer gas includes hydrogen sulfide and ammonia. Sewer gas also contains methane, carbon dioxide, sulfur dioxide, and nitrous oxides
UPC 2015 907.2
1. Can a portion of a yoke vent run horizontally?
2. If it can be run horizontally, can the connection to the soil stack be a combo fitting?
3. Where the yoke vent connects to the vent stack, can that fitting be a combo or a san tee?
Comments:
1. Assuming it's treated like any other vent prior to being above the flood plane (i.e. treated like waste pipe: sloped and not tied together with other vents).
2. If a yoke vent is allowed to be run horizontally, then the portion of the combo that is an inverted wye should satisfy the code. Otherwise separate inverted wye and 1/8th bend will be used.
3. Looking for clarification what is an approved fitting. Explicitly calling out the inverted wye separately from other vent fittings has caused confusion with AHJs.
UPC 2015 905.0, 905.2
Topic: Vent Pipe Connection to Horizontal Drainage Pipe
Would a sanitary tee be an approved fitting where a vent connects to a horizontal drainage pipe below a floor, provided the installation of the branch of the tee, used for the vent connection, conforms to Section 905.2?
Comment
Section 903.3 indicates that changes in direction of vent piping shall be made with appropriate use of approved fittings.
No. Section 905.3 of the 2015 Uniform Plumbing Code states that “Vents less than 6 inches above the flood-level rim of the plumbing fixtures it serves shall be installed with approved draining fittings, material, and grade to drain.” Sanitary Tees are only considered drainage fittings when installed in the vertical position.*
*2015 UPC, 706.2 Horizontal to Vertical. Horizontal drainage lines, connecting with a vertical stack, shall enter through 45 degree (0.79 rad) wye branches, 60 degree (1.05 rad) wye branches, combination wye and one-eighth bend branches, sanitary tee or sanitary tapped tee branches, or other approved fittings of equivalent sweep. No fitting having more than one inlet at the same level shall be used unless such fitting is constructed so that the discharge from one inlet cannot readily enter any other inlet. Double sanitary tees shall be permitted to be used where the barrel of the fitting is not less than two pipe sizes larger than the largest inlet, (pipe sizes recognized for this purpose are 2 inches, 2-1⁄2 inches, 3 inches, 3-1⁄2 inches, 4 inches, 4-1⁄2 inches, 5 inches, 6 inches, etc.) (50 mm, 65 mm, 80 mm, 90 mm, 100 mm, 115 mm, 125 mm, 150 mm, etc.).
UPC 2015 911.0
1. After the circuit vented section can the drain line continue to catch upstream fixtures on the same floor?
2. After the circuit vented section can the drain line continue to catch upstream stacks to upper floors?
3. Or do the stack need to be downstream of the circuit vented section?
Comment:
On circuit venting you can tie in drains to fixture on the same floor to the circuit vent. (example: in a public bathroom where the WC's are circuit vented I can tie in my lav drains to the circuit vented section.)
1. Yes. Section 911.5 of the 2015 Uniform Plumbing Code(UPC)states “fixtures other than the circuit-vented fixtures, are permitted to discharge to the horizontal branch drain. Such fixtures shall be located on the same floor as the circuit-vented fixtures and shall be either individually or common vented”.
2. Per Section 911.5, additional fixtures located on the same floor, may discharge either upstream or downstream of a circuit-vented branch. Waste piping receiving the discharge from fixtures on upper floors would be approved to be connected to the common waste line downstream of the circuit-vented branch.
UPC 2012 906.1
Topic: Air Admittance Valves
Are air admittance valves allowed to be used for venting without taking the vent above the roof?
No. The 2012 Uniform Plumbing Code, does not permit air admittance valves as an acceptable means of venting a drainage system. Section 901.1 requires air circulation throughout all parts of the drainage system by means “vent pipes installed in accordance with the requirements of this chapter and as otherwise required by this code”. This includes termination of each vent pipe through the roof as required in Section 905.4.
Note: Mechanical “check valve” type fittings allow air flow into the waste and vent system when the drain is flowing. Air is unable to flow out through these fittings, thus positive pressure generated downstream of the liquid flowing in the drain line is unable to escape through these “vents”. The purpose of a venting system is to allow air flow to occur in both directions, there stabilizing internal system pressures. Any fitting on a vent pipe which limits air flow to one direction conflicts with basic objectives of a vent piping system.
UPC 2015 907.2
1. Can a portion of a yoke vent run horizontally?
2. If it can be run horizontally, can the connection to the soil stack be a combo fitting?
3. Where the yoke vent connects to the vent stack, can that fitting be a combo or a san tee?
1. Yes. Per Section 905.3 of the 2015 Uniform Plumbing Code (UPC), vents may have horizontal offsets if there are structural conditions prohibiting the vent from being installed vertically. Drainage fittings must be used and grade to the drain for all piping below the flood rim of the fixtures being served.
2. Yes. Section 907.2 requires the yoke vent connection to the drainage stack to be a wye-branch fitting. A combination wye & eighth fitting is a wye-branch fitting.
3. Yes. Section 907.2 does not specify the type of fitting required for the connection of the yoke vent to the vent stack. Section 903.1 requires vent pipe and fittings to comply with applicable standards referenced in Table 701.2.
UPC 2018 909.1
Topic: Special Venting for Island Fixtures
Are the requirements for cleanouts in this section; at the foot vent and at the 2-inch vertical drain (by reference Section 707.4) affected by the 707.4 Exceptions (3)?
2 Are cleanouts required in the vertical portion of foot vents serving fixtures above the first floor.
3. If cleanouts serving foot vents are not required above the first floor in the 2018 and previous editions of the UPC, will they continue to be exempted in the 2021 UPC where the language in exception 3 has be amended?
1. Yes. Per Section 707.4(3) of the 2018 Uniform Plumbing Code (UPC), cleanouts may be omitted on all fixtures, except urinals, located above the floor level of the lowest floor of the building.
2. No. Section 707.4(3) does not specifically address cleanouts for sinks, including island sinks, therefore the cleanout on the foot vent would not be required.
3. No. Section 707.4(3) of the 2021 Uniform Plumbing Code (UPC) states, “Excepting the building drain, its horizontal branches, kitchen sinks and urinals, a cleanout shall not be required on a pipe or piping that is above the floor level of the lowest floor of the building”. The Code change would require a cleanout on the foot vent.
UPC 2015 907.1
Topic: Vent Stacks, Relief Vents, Drainage Stack
May multiple waste stacks (Sanitary Waste & Graywater), share a common parallel vent stack?
Comment:
If they are allowed to share a common vent stack, does each waste stack need to be connected independently to the vent via a yoke vent, or can the yoke vents combine?
Gray water drains and sanitary drains are both waste water drains. The fixtures for both are required to be trapped and vented per applicable sections of the 2015 Uniform Plumbing Code. The Code does not prohibits the use of a common vent.
UPC 2015 911.0, 1014.0, 1014.1.1
Topic: Circuit Venting Grease Interceptors
1. Is circuiting venting an approved manner of venting a series of fixtures connected to a grease interceptor?
Circuit venting is an approved manner to vent up to a maximum of 8 fixtures such as water closets, floor drains, bathtubs and shower stalls. Restaurant equipment may not be circuit vented due to their grease producing potential. Per section 1014.1.1 of the 2015 UPC, each fixture discharging into a grease interceptor shall be individually trapped and vented in an approved manner. Also grease lines are not permitted to be a combination waste and vent system because of the type of grease waste migrating into the vents and thus affecting the venting.
UPC 2003 906.2
UPC 2006 906.2
UPC 2009 906.2
UPC 2012 906.2
UPC 2015 906.2
What is the code requirement for the distance a terminating vent on roof needs to be from the fresh air intake of a HVAC unit?
Per Section 906.2 of the 2015 UPC, each vent shall terminate not less than 10 feet from, or not less than 3 feet above an openable window, door, opening, air intake, or vent shaft.
UPC 2003 909.0
UPC 2006 909.0
UPC 2009 909.0
UPC 2012 909.1
UPC 2015 909.1
Topic: Special Venting for Island Fixtures
What is the required vent size under the sink (not the foot vent)?
Per Section 909.1 of the 2015 UPC, pipe sizing for island drains “shall be as elsewhere in this code”. Sizing requirements for drainage and vent piping may be found in Tables 702.1 and 703.2. A domestic kitchen sink drain has an assigned drainage fixture unit value of two, requiring a minimum 2” waste line and 1-1/2” vent.
Note: The 2015 Illustrated Training Manual, Figure 909.1B shows a code compliant drawing of an island sink installation.
UPC 2021 908.2.4
Topic: Horizontal Wet venting
In regards to horizontal wet venting, does the water closet need to be the furthest fixture downstream on a horizontally wet vented line?
Yes, the fixtures allowed to be vented by a horizontal wet vent either have low discharge surges or last for only a short duration that do not significantly impact the air flow in the horizontal drain. That is why the water closet is distinguished from the other fixtures with the requirement to connect downstream of all the fixture drain connections to the horizontal wet vent.
UPC 2021 909.1
Topic: Special venting for island fixtures
Is it acceptable to use a sanitary tee to tie in the foot vent to the vertical fixture vent on a island loop vent?
No, The foot vent shall be taken off of the vertical fixture vent by means of a wye branch fitting immediately below the floor. The wye branch fitting connecting the return vent to the foot vent is to be in vertical position with the wye-branch sloping down toward the drain rather than up toward the vent, which would better assist air flow. A sanitary tee is a drainage fitting when installed in the vertical position, but it is connected to a trap arm and not allowable for the special venting of an island fixture.
UPC 2018 908.2
Topic: Horizontal Wet Venting for a Bathroom Group
Could a Wye at the end of a horizontal wet vent in a bathroom group be in the vertical position, when it's picking up a water closet?
No, the purpose of a horizontal wet vent is to permit multiple fixtures to be served by a common horizontal waste line, that also acts as the vent for the fixtures. The connection of fittings to a horizontal wet vented system, as indicated by the system’s description, are intended to remain horizontal, so as not to interfere with the continuous air space above the water surface in drain.